Larsen Fire Hose Cabinets

Models HC3030 and HC3234 SERIES

TO SPECIFY THE HC3030 and HC3234 SERIES:

  • Insert, after “HC” the appropriate prefix for the trim and door material.
    • “S” – STEEL
    • “AL” – ALUMINUM
    • “SS” – STAINLESS STEEL
    • “B” – BRASS
    • “BZ” – BRONZE (Brass and Bronze available only in the HC3030 Series)
  • Select the required model number from the table below.
  • Select the door style from the illustrations.
Larsen fire hose cabinets HC series with steel, aluminum and stainless options
Larsen fire hose cabinets HC series with steel, aluminum and stainless options

Dimensions

Model
Number
Trim Style
and
Projection
Inside Box
Dimensions*
H x W x D
Outside Trim
Dimensions
H x W***
Rough
Opening
H x W x D
Knockout
Locations**
E   F   G
Interior
Capacity
  HC3030-R Rec. 5/16 30 x 30 x 8 33½ x 33½ 31 x 31 x 8¼ 4″ 4″ 4″ One hose
rack unit
with
100 ft. of
rack hose
and a fire
extinguisher
FS HC3030-R Rec. 5/16 30 x 30 x 8 33½ x 33½ 321/8 x 321/8 x 91/8
  HC3030-RK Semi-Rec. 1¼ 30 x 30 x 8 33½ x 33½ 31 x 31 x 7¼ 4″ 4″ 4″
FS HC3030-RK Semi-Rec. 1¼ 30 x 30 x 8 33½ x 33½ 321/8 x 321/8 x 81/8
  HC3030-RL Semi-Rec. 2½ 30 x 30 x 8 33½ x 33½ 31 x 31 x 6 4″ 4″ 4″
FS HC3030-RL Semi-Rec. 2½ 30 x 30 x 8 33½ x 33½ 321/8 x 321/8 x 7
  HC3030-RT Trimless 30 x 30 x 8 –x –x8½† 4″ 4″ 4″
  HC3030-SM Surface Mtd. 33½ x 33½ x 8½ 33½ x 33½
  HC3232-R Rec. 5/16 32 x 32 x 8 35½ x 35½ 33 x 33 x 8¼ 4″ 4″ 4″ One hose
rack unit
with
100 ft. of
rack hose
and a fire
extinguisher
FS HC3232-R Rec. 5/16 32 x 32 x 8 35½ x 35½ 341/8 x 341/8 x 91/8
  HC3232-RK Semi-Rec. 1¼ 32 x 32 x 8 35½ x 35½ 33 x 33 x 7¼ 4″ 4″ 4″
FS HC3232-RK Semi-Rec. 1¼ 32 x 32 x 8 35½ x 35½ 341/8 x 341/8 x 81/8
  HC3232-RL Semi-Rec. 2½ 32 x 32 x 8 35½ x 35½ 33 x 33 x 6 4″ 4″ 4″
FS HC3232-RL Semi-Rec. 2½ 32 x 32 x 8 35½ x 35½ 341/8 x 341/8 x 7
  HC3232-RT Trimless 32 x 32 x 8 –x –x8½† 4″ 4″ 4″
  HC3232-SM Surface Mtd. 35½ x 35½ x 8½ 35½ x 35½
  HC3234-R Rec. 5/16 34 x 32 x 8 37½ x 35½ 35 x 33 x 8¼ 4″ 4″ 4″ One hose
rack unit
with
100 ft. of
rack hose
and a fire
extinguisher
FS HC3234-R Rec. 5/16 34 x 32 x 8 337½ x 35½ 361/8 x 341/8 x 91/8
  HC3234-RK Semi-Rec. 1¼ 34 x 32 x 8 37½ x 35½ 35 x 33 x 7¼ 4″ 4″ 4″
FS HC3234-RK Semi-Rec. 1¼ 34 x 32 x 8 37½ x 35½ 361/8 x 341/8 x 81/8
  HC3234-RL Semi-Rec. 2½ 34 x 32 x 8 37½ x 35½ 35 x 33 x 6 4″ 4″ 4″
FS HC3234-RL Semi-Rec. 2½ 34 x 32 x 8 37½ x 35½ 361/8 x 341/8 x 7
  HC3234-RT Trimless 34 x 32 x 8 –x –x8½† 4″ 4″ 4″
  HC3234-SM Surface Mtd. 37½ x 35½ x 8½ 37½ x 35½

NOTE: “FS” models denote Larsen’s “Flame-Shield” fire-rated cabinets. When specifying Larsen’s “Flame-Shield” fire-rated cabinet option for valve and hose cabinets, refer to the dimension chart and select from the models with an “FS” prefix. No knock-outs are provided with fire-rated valve and hose cabinets. Pipe holes must be drilled by installer and complete instructions are supplied with each fire-rated valve and hose cabinet.

Model HC3238 and HC3242 SERIES

TO SPECIFY THE HC3238 and HC3242 SERIES:

  1. Insert, after “HC,” the appropriate prefix for the trim and door material.
    • “S” – STEEL 
    • “AL” – ALUMINUM 
    • “SS” – STAINLESS STEEL
  2. Select the required model number from the table below.
  3. Select the door style from the illustrations.
Larsen fire hose cabinets HC series with steel, aluminum and stainless options
Larsen fire hose cabinets HC series with steel, aluminum and stainless options

Dimensions

Model
Number
Trim Style
and
Projection
Inside Box
Dimensions*
H x W x D
Outside Trim
Dimensions
H x W***
Rough
Opening
H x W x D
Knockout
Locations**
E   F   G
Interior
Capacity
  HC3238-R Rec. 5/16 38 x 32 x 8 41½ x 35½ 39 x 33 x 8¼ 4″ 4″ 4″ One hose
rack unit
with
100 ft. of
rack hose,
fire ext.
and a
Fire Dept.
valve
FS HC3238-R Rec. 5/16 38 x 32 x 8 41½ x 35½ 401/8 x 341/8 x 91/8
  HC3238-RK Semi-Rec. 1¼ 38 x 32 x 8 41½ x 35½ 39 x 33 x 7¼ 4″ 4″ 4″
FS HC3238-RK Semi-Rec. 1¼ 38 x 32 x 8 41½ x 35½ 401/8 x 341/8 x 81/8
  HC3238-RL Semi-Rec. 2½ 38 x 32 x 8 41½ x 35½ 39 x 33 x 6 4″ 4″ 4″
FS HC3238-RL Semi-Rec. 2½ 38 x 32 x 8 41½ x 35½ 401/8 x 341/8 x 7
  HC3238-RT Trimless 38 x 32 x 8 –x –x8½† 4″ 4″ 4″
  HC3238-SM Surface Mtd. 41½ x 35½ x 8½ 41½ x 35½
  HC3242-R Rec. 5/16 42 x 32 x 8 45½ x 35½ 43 x 33 x 8¼ 4″ 4″ 4″ One hose
rack unit
with
125 ft. of
rack hose,
fire ext.
and a Fire Dept.
valve
FS HC3242-R Rec. 5/16 42 x 32 x 8 45½ x 35½ 441/8 x 341/8 x 91/8
  HC3242-RK Semi-Rec. 1¼ 42 x 32 x 8 45½ x 35½ 43 x 33 x 7¼ 4″ 4″ 4″
FS HC3242-RK Semi-Rec. 1¼ 42 x 32 x 8 45½ x 35½; 441/8 x 341/8 x 81/8
  HC3242-RL Semi-Rec. 2½ 42 x 32 x 8 45½ x 35½ 43 x 33 x 6 4″ 4″ 4″
FS HC3242-RL Semi-Rec. 2½ 42 x 32 x 8 45½ x 35½ 441/8 x 341/8 x 7
  HC3242-RT Trimless 42 x 32 x 8 –x –x8½† 4″ 4″ 4″
  HC3242-SM Surface Mtd. 45½ x 35½ x 8½ 45½ x 35½

* All Hose Cabinets are available with 6″ deep box, at no charge, if specified.
** No knockouts are provided for surface-mounted cabinets unless specified.
† Trimless cabinets must be installed before the drywall. Plaster stop must be behind the drywall. Trimless are not recommended for block wall installation.
*** Deduct ¾” from HxW Dimensions for Cabinets with Aluminum Door & Trim. This does not apply to “FS” fire-rated option.